-40%
Schneider RE8TA31BU Timing Relay, 0.3-30s, Type A, 24V AC/DC, 110-240 VAC, 1 C/O
$ 26.4
- Description
- Size Guide
Description
First, And this is important.I have been selling for 20 years and have had no Negative or even Neutral reviews. ALWAYS POSITIVE.
Any Item may be returned up to 30 days after delivery for a refund. If it's dead, send it back. I’ll even eat the shipping.
Main
range of product
Zelio Time
product or component type
Optimum industrial timing relay
component name
RE8
time delay type
A
time delay range
0.3...30 s
sale per indivisible quantity
1
Complementary
discrete output type
Relay
contacts material
Silver nickel contacts
width pitch dimension
22.5 mm
[Us] rated supply voltage
110...240 V AC 50/60 Hz
24 V AC/DC 50/60 Hz
voltage range
0.9...1.1 Us
connections - terminals
Screw terminals, 2 x 1.5 mm² flexible with cable end
Screw terminals, 2 x 2.5 mm² flexible without cable end
tightening torque
0.6…1.1 N.m
setting accuracy of time delay
+/- 20 % of full scale
repeat accuracy
< 1 %
voltage drift
< 2.5 %/V
temperature drift
< 0.2 %/°C
minimum pulse duration
26 ms
reset time
50 ms
maximum switching voltage
250 V
mechanical durability
20000000 cycles
[Ith] conventional free air thermal current
8 A
maximum [Ie] rated operational current
2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991
2 A DC-13 24 V at 70 °C conforming to VDE 0660
3 A AC-15 24 V at 70 °C conforming to IEC 60947-5-1/1991
3 A AC-15 24 V at 70 °C conforming to VDE 0660
0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991
0.1 A DC-13 250 V at 70 °C conforming to VDE 0660
0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991
0.2 A DC-13 115 V at 70 °C conforming to VDE 0660
minimum switching capacity
at 12 V 10 mA
marking
CE
overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to CSA
supply disconnection value
> 0.1 Uc
operating position
Any position without derating
surge withstand
2 kV conforming to IEC 61000-4-5 level 3
power consumption in VA
0.7 VA at 24 V
1.8 VA at 110 V
8.5 VA at 240 V
maximum power consumption in W
0.5 W at 24 V
terminal description
ALT
(A1-B1)CO
(15-16-18)OC_OFF
height
78 mm
width
22.5 mm
depth
80 mm
net weight
0.11 kg
Environment
immunity to microbreaks
3 ms
standards
EN/IEC 61812-1
product certifications
CSA
UL
GL
ambient air temperature for storage
-40…85 °C
ambient air temperature for operation
-20…60 °C
relative humidity
15…85 % 3K3 conforming to IEC 60721-3-3
vibration resistance
0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6
IP degree of protection
IP20 (terminals)
IP50 (casing)
pollution degree
3 conforming to IEC 60664-1
dielectric test voltage
2.5 kV
non-dissipating shock wave
4.8 kV
resistance to electromagnetic fields
10 V/m conforming to IEC 61000-4-3 level 3
resistance to fast transients
2 kV conforming to IEC 61000-4-4 level 3
disturbance radiated/conducted
CISPR 22 - class A
CISPR 11 group 1 - class A